Function
Contactors are electromechanically
controlled switches used to control
single or multi-phase (high) power
loads while the control itself can
be (very) low power.
Applications
Switching of lighting, heating-equipment, motors for pumps and fans, ...
Day and night contactors are used mainly in combination with dual-tariff
applications to allow high-energy-loads (i.e. electrical water heaters,
accumulation heaters) only to consume energy during the low-tariff period.
A forced-on, forced-off, auto-switch allows to overrule the normal operation of
the DN-contactor at all times.
Features
Except for the 20A version, all contactors have DC coils, resulting in an abso-
lutely noise-free, real silent operation: 50 or 60Hz noise generation by the con-
tactor is impossible. As all DC coil contactors have an internal diode rectifier
bridge, they all can be operated by both DC and AC power supplies. The built-
in varistor protects the coil against an overvoltage of up to 5kV.
The switch position of the contactor is visualised through an indicator flag.
The loss-proof safety terminals are equipped with Pozidriv screws and have
IP20 protection degree. Add-on auxiliary contacts as well as spacers and
sealing pieces are available.
Standards
IEC 60947-4-1, BS EN 60947-4-1, IEC 61095, BS EN 61095. Approval VDE.
Contax
Contactors
Performance
Rated switching capacity
Contacts
Switching capacity for different loads
Rated insulation voltage
Rated operational voltage
Switching-on capacity
cos ϕ = 0.65 at 380-400V 3phase
cos ϕ = 0.95 at 220-230V 1phase
Switching-off capacity
cos ϕ = 0.65 at 380-400V 3phase
cos ϕ = 0.95 at 220-230V 1phase
Fuse type GL for short-circuit protection
Ohmic loss per contact at In
Maximum switching frequency AC1 / AC7a
Maximum switching frequency AC3 / AC7b
Mechanical service life
Electrical service life AC1 / AC7a
Electrical service life AC3 / AC7b
Screws
Terminal capacity: min
max
Magnetic control system
Control voltage range
Rated operating frequency
Operating temperature range
Maximum pull-in coil power loss
Maximum holding coil power loss
Switching-on delay
Switching-off delay
Screws
Terminal capacity: min
max
20A
400V
250V
-
100A
-
80A
20A
1.0W
300/h
600/h
10
6
150000
150000
Pozidriv 1
1x1 mm
2
1x10mm
2
or 2x4 mm
2
85 ... 110%xUn
50 or 60Hz
-25 ... +55°C
(1)
8.0VA / 5.0W
3.2VA / 1.2W
9 ... 12 ms
10 ... 12 ms
Pozidriv 1
1x1 mm
2
1x4mm
2
or 2x2
.5
mm
2
24A
500V
440V
90A
-
72A
-
35A
1.5W
300/h
600/h
10
6
150000
500000
Pozidriv 1
1x1 mm
2
1x10mm
2
or 2x4 mm
2
85 ... 110%xUn
DC, 40 ... 450Hz
-25 ... +55°C
(1)
4VA / 4W
4VA / 4W
< 40 ms
< 40 ms
Pozidriv 1
1x1 mm
2
1x4mm
2
or 2x2
.5
mm
2
40A
500V
440V
220A
-
176A
-
63A
3.0W
300/h
600/h
10
6
150000
170000
Pozidriv 2
1x1.5 mm
2
1x25mm
2
or 2x10 mm
2
85 ... 110%xUn
DC, 40 ... 450Hz
-25 ... +55°C
(1)
5VA / 5W
5VA / 5W
< 40 ms
< 40 ms
Pozidriv 1
1x1 mm
2
1x4mm
2
or 2x2
.5
mm
2
63A
500V
440V
300A
-
240A
-
80A
6.0W
300/h
600/h
10
6
150000
240000
Pozidriv 2
1x1.5 mm
2
1x25mm
2
or 2x10 mm
2
85 ... 110%xUn
DC, 40 ... 450Hz
-25 ... +55°C
(1)
6.5VA / 6.5W
4.2VA / 4.2W
< 40 ms
< 40 ms
Pozidriv 1
1x1 mm
2
1x4mm
2
or 2x2
.5
mm
2
Remark: If several contactors are mounted next to each-other and the time of operation exceeds 1 hour and the ambient
temperature rises above 40°C, a 1/2-module spacer must be added every second contactor (I.e. contactor contactor spacer
contactor contactor spacer contactor contactor etc.)