SW Plus 2524 & SW Plus 2548
Xantrex Sine Wave Plus Inverter/Charger
Electrical Specications
SW Plus 2524 SW Plus 2548
AC Input Voltage (nominal) 120 VAC 120 VAC
AC Input Voltage Range, adjustable 80-150 VAC 80-150 VAC
AC Input Current 60 amps AC pass through / 20 amps AC charging 60 amps AC pass through / 20 amps AC charging
Continuous Power @ 40 °C 2500 watts 2500 watts
Efficiency (peak in Inverter mode) 95% 95%
Efficiency (Invert mode) Over 90% from 120W to 2000W Over 90% from 160W to 2500W
Inverter Voltage Regulation ± 3% ± 3%
Frequency (Nominal ± 0.04% Crystal Controlled) Inverter mode 60 Hz 60 Hz
Continuous Output Current (@ 25 °C) 21 A rms 21 A rms
Current Surge Capability@ 25 °C
5 Sec Rating 80 A rms 80 A rms
Over current trip point 125 A peak 175 A peak
Inverter Voltage THD (Resistive load) < 5% < 5%
Automatic Transfer Relay 60 A rms 60 A rms
DC Input Voltage (Nominal) 25.2 VDC 50.4 VDC
DC Input Voltage Range 22-32 VDC 44-64 VDC
DC Current at Rated Power (Inverter mode), 120 amps DC 60 amps DC
internal temperature stabilized
Idle Consumption (Typical at full voltage) < 16 watts < 20 watts
Search Mode Consumption (Typical at full voltage) < 2 watt < 2 watt
Continuous Charge Rate@ 120VAC input (See Note 1 below) 70 amps DC 40 amps DC
Features
Forced Air Cooling Standard variable speed brushless DC fans
Multi-stage charging Bulk, absorption, float/ silent, and equalize
Control Panel Standard built-in, two line, backlit, alphanumeric LCD with 8 LED indicators
Battery Temperature Sensor (BTS) BTS - standard remote battery temperature sensor for increased battery performance
Common Specications
Mechanical Specications
Operating Temperature Range
Unit will meet specifications 32 °F to 77 °F (0 °C to 25 °C)
Unit may not meet specifications -13 °F to 140 °F (-25 °C to 60 °C)
Storage -67 °F to 284 °F (-55 °C to 140 °C)
Enclosure Type Indoor, ventilated, Galvaneel chassis with powdercoat finish
Unit Weight 105 lb (48 kg)
Shipping Weight 111 lb (50 kg)
Inverter Dimensions (H x W x D) 15” x 22.5” x 9” (38 cm x 57 cm x 23 cm)
Shipping Dimensions (H x W x D) 20” x 27” x 15” (52 cm x 69 cm x 40 cm)
Mounting Wall Mount/Shelf
Waveform Sine wave, 34 to 52 steps per cycle
Load Sensing (Inverter Mode) Adjustable 8 to 248 watts (8 watts default)
Listings CSA listed to UL 1741 and CSA107.1 FCC Class B
Note 1: This is a continuous charge current rating. The peak charge current is higher, particularly before the unit has warmed up. Peak charge current will vary as a function of temperature and the AC input voltage.
Specifications subject to change without notice.
Options
Generator Start Module (GSM) Automatic generator control system for two and three wire start AC and DC generators
Auxiliary Load Module (ALM) User adjustable voltage controlled signal relays for control of loads or charging sources
Remote Inverter Control Module (ICM) Optional full function remote control with LCD and LED indicators
RC8 Optional remote on/off with indicator
Stacking Interface (SWI) Optional cable for series stacking of two identical SW Plus units for 120/240 VAC output
DC Conduit Box (DCCB) Optional side mount conduit box for code-compliant DC wiring connections (USA)
DC Conduit Box Fused (DCCB-F) Optional side mount conduit box for code-compliant DC wiring connections with fuse (Canada)
AC Conduit Box (ACCB) Optional side mount conduit box for code-compliant AC wiring (bypass/disconnect circuit breakers)