Multiple Unit Configuration
975-0637-01-01 Rev B 1–29
This guide for use by qualified personnel only
Multiple Unit Configuration
The Conext SW inverter/chargers supports multiple unit configuration to increase
power output. This gives the system engineer and/or installer more options to
work with when tailoring a system to meet load demands. Multiple inverter/
chargers of different power levels can be installed in a system as stand alone or
in parallel.
In a multiple unit configuration, only two Conext SW inverter/chargers of the same
model can be used. For example, two Conext SW 4024 230 units can be
configured because both units each have a 24-volt rating and a power rating of
up to 3500 watts.
In this configuration, the inverter and charger capacity of a system is doubled. In
the case of two Conext SW 4024 230 units, the inverter power rating doubles to
7000 watts and the charging output current doubles to 180 amps. However, the
AC transfer relay rating of 30-amps remains the same. Inverter/chargers can
operate from different battery banks, meaning each unit is connected to its own
battery bank. However, it is highly recommended to use only a single battery
bank. See “DC Connections for Multiple Unit Configuration” on page 1–30.
Figure 1-14 Multiple Unit Configuration Using Two Conext SW Units
L
NEUTRAL
GROUND
NEUTRAL
GROUND
30A
30A