Installation
1–32 975-0637-01-01 Rev B
This guide for use by qualified personnel only
Configuring the System for Multiple Unit Operation
Verify all DC and AC connections. Check Xanbus network connections and
ensure that terminators are installed at devices at each end of the network. The
simplest system includes a Xanbus SCP, the two multi-unit-configured Conext
SW inverter/chargers, and two Xanbus terminators.
For both units to operate in multiple unit configuration, a Master and Slave have
to be assigned. The default out-of-box configuration for all Conext SW inverter/
chargers is Master which causes a conflict the first time the system is powered
up. The installer will need to change configuration on one of the inverter/chargers
to Slave mode.
To configure the system for multiple unit configuration:
1. Apply DC power to both inverter/chargers.
Power up order has no impact. Because there are now two Master units in
the system, the SCP will detect an F71 fault, a “system configuration fault”.
2. From the SCP System Status screen, press Enter. The Select Device screen
appears.
3. Select the inverter to configure as a Slave unit from the list, then press Enter.
4. Bring up the Advanced Settings screen by pressing Enter, Up, and Down
arrow buttons all together.
5. Select Advanced Settings and press Enter. The Advanced Settings screen
appears.
6. Scroll down to select Multi Unit Config.
At this point all devices in the system will be automatically placed in standby
mode. All three LEDs on the inverter to be configured will start flashing
7. Select Invtr Mode and press Enter.
8. Select Slave and press Enter.
9. Press the Exit button repeatedly until the System Status screen appears.
NOTE: The only situation in which the Slave may shut down the Master inverter
is during fault detection conditions such as high or low battery voltage,
overcurrent, or over-temperature conditions. Both inverters will auto reset after a
fault detection condition has been cleared. The exception is that an overcurrent
condition will generate a shutdown for both inverters that will require a manual
restart of the system.
Figure 1-17 Multi Menu Screen
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
Gen Support
Multi Unit Config
Restore Defaults
Adv Features
CSW4024E 00: Multi
Dev Name
Dev Number
Invtr Mode
Battery
[00]
[01]
[Master]
[HouseBatt1]
[*Master] [Slave]
[*HouseBatt1]...[HouseBatt5]
ConextSWEUROInstallationGuide.book Page 32 Wednesday, December 5, 2012 10:55 AM