Installation
1–36 975-0639-01-01 Rev A
This guide for use by qualified personnel only
Search Mode Operation in Multiple Unit Configuration
When two inverter/chargers are configured, search mode behavior on the Slave unit is
modified and is dependent on how much total load is on the system.
Disabling Search Mode on the Master Unit
Search mode on the Master unit will not function properly. When the Master sends out a
load search pulse, a small current also flows into the output of the Slave unit since the
two outputs are in parallel. This Master unit falsely detects a load causing erratic search
mode operation. For this reason, it is highly recommended to disable search mode on
the Master unit.
Setting Search Mode on the Slave Unit
The Slave unit will behave in one of two ways depending on whether its search mode is
enabled or disabled.
Search mode enabled This is the recommended mode which helps minimize battery
draw. The Slave unit continuously monitors the output of the Master unit. If the Master
unit has more than 60% of the rated load (for example, 2100 watts on SW 4024 120/
240), the Slave unit will assist the Master and the two will share the load equally. Should
the load on the Master drop below 20% of rated load (700 watts for SW 4024 120/240),
the Slave unit disengages and returns to a waiting state.
Search mode disabled The Slave unit operates continuously along with the Master
unit and shares the load.
Wiring Schematic
NOTE: Please refer to “Multiple Unit Configuration” on page 1–32 that shows the wiring
schematic employed between two Conext SW inverter/chargers.
IMPORTANT: Follow the same guidelines in “Inverter/Charger Installation” on page 1–
18 when choosing cables and/or wires for AC and DC connections.
FIRE, ELECTRICAL SHOCK, AND EXPLOSION HAZARD
Make sure all wiring being used to make multiple unit configurations between
inverter/chargers is disconnected (physically or by opening and locking out
the breaker) from all electrical sources before handling. All wiring must be
done in accordance with local and national electrical wiring codes.
Failure to follow these instructions will result in death or serious injury.